FLM‑420‑O1I1 Output-input Interface Modules

دریافت دیتاشیت

Technical Specifications
Electrical LSN
• LSN input voltage 15 V DC to 33 V DC
• Max. current consumption from LSN 1.9 mA
Output
• Max. switchable voltage of
semi-conductor output
30 V DC
• Max. switchable output current 700 mA (depending on external
power supply)
• External power supply 5 V DC to 30 V DC
Input
Line monitoring with EOL
• EOL resistor Nominal 3.9 kΩ
• Overall line resistance RΣ
with RΣ = RL/1 + RL/ 2 + REOL
• Standby: 1500 Ω to 6000 Ω
• Short circuit: < 800 Ω
• Line interruption: > 12.000 Ω
Contact monitoring
• Max. current strength (current pulse) 8 mA
Minimum activation time of the input 3.2 s
Mechanics Connections
• FLM-420-O1I1-E 14 screw terminals
• FLM-420-O1I1-D 12 screw terminals
Permissible wire diameter
• FLM-420- O1I1-E 0.6 mm2 to 2.0 mm2
• FLM-420- O1I-D 0.6 mm2 to 3.3 mm2
Address setting
• FLM-420- O1I1-E 8 DIP switches
• FLM-420- O1I1-D 3 rotary switches
Housing material
• FLM-420- O1I1-E ABS/PC blend
• FLM-420- O1I1-D incl. adapter PPO (Noryl)
Housing color
• FLM-420- O1I1-E Signal white, RAL 9003
• FLM-420- O1I1-D incl. adapter Gray white, similar to RAL 9002
Dimensions
• FLM-420- O1I1-E Approx. 50 mm x 22 mm (Ø x H)
• FLM-420- O1I1-D incl. adapter Approx. 110 x 110 x 48 mm
(W x H x D)
Weight Without/with packing
• FLM-420- O1I1-E Approx. 35 g / 170 g
• FLM-420-O2-D Approx. 95 g / 390 g
Environmental conditions Permissible operating temperature -20 °C to +65 °C
Permissible storage temperature  -25 °C to +80 °C
Permissible rel. humidity < 96% (non-condensing)
Classes of equipment as per IEC 60950 Class III equipment
Protection class as per IEC 60529 IP 30
System limiting values Maximum cable length input 3 m
Maximum cable length output 3 m