FLM-420-I8R1-S Octo-input interface module with relay

دریافت دیتاشیت

Technical Specifications
Electrical LSN input voltage (V DC) 15 … 33
Max. current consumption from LSN (mA) 5.5
Inputs, independent 8
Line monitoring: EOL resistor,
 nominal (kΩ) Detected line
conditions (Ω) with overall
Line resistance RΣ = RL/1 + RL/2 + REOL
3.9 Standby: 1500 … 6000
Interruption: > 12000
Short circuit: < 800
Contact monitoring: Max. current
consumption (mA)
8
Min. activation time of the inputs IN 1…8 (s) 3.2
Change-over relay, low voltage NC / COM, COM / NO
Contact load:
Max. switching capacity (A / V DC; A / V AC)
Min. switching capacity (mA / mV DC; mA / mV AC) Max. frequency (Hz)
2 / 30; 0.5 / 42.4
0.01 / 10; 0.01 / 10
100
Connections Screw terminals
Rotary switches, number 3
Weight, without/with packing (g) 480 / 800
Dimensions W x H x D (mm) 140 x 200 x 48
Wire gauge (mm2 ) 0.6…3.3
Housing material, housing color (RAL) ABS+PC-FR, RAL 9003
Environmental Operating temperature (°C) -20 …+65
Storage temperature (°C) -25 …+80
Rel. humidity (%), non-condensing < 96 %
Class of equipment (IEC 60950) III
Degree of protection (IEC 60529) IP 54
System limits Max. cable length, not electrically isolated
from LSN in total (m)
500