FLM‑420‑NAC Signaling Device Interface Modules
Technical Specifications | ||
Electrical | Input voltage | 15 V DC to 33 V DC |
Max. current consumption | ||
• from LSN | 6,06 mA (normal operation and alarm) | |
• from external power supply | 15 mA (normal operation) + output current | |
External power supply | 20,4 V DC to 29 V DC | |
Max. output current | 3 A (during an alarm, from ext. power supply) |
|
EOL resistance | 3.9 kΩ | |
Mechanical | Display elements | |
• Red LED | Alarm | |
• Green LED | Normal operation | |
LSN/Address setting | 3 rotary switches for | |
• Mode LSN "classic" or LSN improved version |
||
• Automatic or manual addressing | ||
Connections | 12 threaded clamps | |
Max. wire diameter for terminals |
3.3 mm2 (12 AWG) | |
Housing materia | ||
• Interface module | PPO (Noryl) | |
• Surface-mount housing | ABS/PC-Blend | |
Housing color | ||
• Interface module | Off-white, similar to RAL 9002 | |
• Surface-mount housing | • Surface-mount housing | |
Dimensions | ||
• FLM-420-NAC-S | Approx. 126 x 126 x 71 mm (4.96 x 4.96 x 2.8 in.) |
|
• FLM-420-NAC-D (with DIN rail adapter) |
Approx. 110 x 110 x 48 mm (4.33 x 4.33 x 1.89 in.) |
|
Weight | ||
FLM-420-NAC-S | Approx. 390 g (13.8 ounces) | |
FLM-420-NAC-D (with DIN rail adapter) |
Approx. 150 g (5.3 ounces) | |
System limits | Number of zones per signaling device interface module | 1 |
Environmental conditions | Permitted operating temperature |
-20 °C to 50 °C (-4 °F to 122 °F) |
Permitted storage temperature |
-25 °C to 80 °C (-13 °F to 176 °F) |
|
Permitted relative humidity | < 96% | |
Classes of equipment as per IEC 60950 |
Class III equipment | |
Protection class as per IEC 60529 | ||
• FLM-420-NAC-S | IP 54 | |
• FLM-420-NAC-D | IP 30 |