FLM‑420/4‑CON Conventional Interface Modules 4‑wire LSN

دریافت دیتاشیت

Technical Specifications
Electrical LSN
• LSN input voltage e 15 V DC to 33 V DC (min. to max.)
• Max. current consumption from LSN 8.5 mA
Primary line
• Line voltage 21 to 22 V DC (21.5 V DC typ. ±0.5 V DC))
• Max. current supply 2- wire sensor 6 mA
• Max. line current 80 mA per line (±10% at 25 °C)
• Max. line resistance 50 Ω per line (max. 2 x 25 Ω)
• Galvanic isolation from LSN Yes
Input power supply (PWR IN)
• Voltage 24 to 30 V DC
• Residual ripple < 150 mV
Output power supply 4‑wire detector (AUX)
• Voltage 23.5 V DC to 30 V DC
(rated voltage 24 V DC)
• Residual ripple < 300 mV
• Max. current (supply to
4‑wire detector)
200 mA per output
(can be switched in parallel)
EOL resistor for stub wiring of conventional zone (class B)
• With calibration value 2.2 kΩ
• Without calibration value 2.2 kΩ / 3.9 kΩ
Mechanics Display element 1 red LED, flashes at 1 Hz in
the event of an alarm
Address setting 3 rotary switches
Connections 12 screw terminals
Permitted wire cross-section 0.6 to 3.3 mm2
Housing materia
• Surface-mounted housing ABS/PC blend
• Interface housing and adapte PPO (Noryl)
Color
• Surface-mounted housing Signal white, RAL 9003
• Interface housing and adapter Off- white, similar to RAL 9002
Dimensions
• FLM-420/4-CON-S Approx. 126 x 126 x 71 mm (W x H x D)
• FLM-420/4-CON-D Approx. 110 x 110 x 48 mm (W x H x D)
Weight Without / with packaging
• FLM-420/4-CON-S Approx. 390 g / 590 g
• FLM-420/4-CON-D Approx. 150 g / 350 g
Environmental conditions Permitted operating temperature -20 °C to +55 °C
Permitted storage temperature -25 °C to +80 °C
Permitted rel. humidity < 96% (non-condensing)
Classes of equipment as per IEC 60950 Class III equipment
Protection class as per IEC 60529
• FLM-420/4-CON-S IP 54
• FLM-420/4-CON-D IP 30