FAS-420-TM Series Aspirating Smoke Detectors LSN improved version

دریافت دیتاشیت

Technical Specifications
Electrical LSN power supply 15 V DC . . 33 V DC
Auxiliary power supply 15 V DC . . 30 V DC
LSN current consumption 6.25 mA
Current consumption from Fan voltage
auxiliary power supply 9 V      10.5 V     12 V
- Starting current 150 mA     150 mA     150 mA
- In standby 105 mA 125 mA 145 mA
- With alarm,
device variants FAS‑420‑TM
 and FAS‑420‑TM‑R
110 mA      130 mA     150 mA
- With alarm, device variant
FAS‑420‑TM‑RVB
140 mA     160 mA       180 mA
Displays on the device  - FAS‑420‑TM ,  FAS‑420‑TM‑R   ,  FAS‑420‑TM‑RVB
Operation Green LED   ,Green LED              , Green LED
Malfunction Yellow LED   ,Yellow LED         ,Yellow LED
Alarm Red LED      ,Red LED    ,2 red LEDs (pre-alarm and main alarm)
Fire location display   -  ,5 red LEDs(zones A-E)   ,5 red LEDs(zones A-E)
Smoke level display -  ,  -    , Yellow smoke level displaywith 10 segments(1-10)
Infrared port IR transmitter/receiver   ,IR transmitter/receiver ,  IR transmitter/receiver
'Mechanics Conical duct connections Ø 25 mm 1x aspiration pipe
1x air return
• Aspiration pipe 1 pipe
• Air return 1 pipe
Cable bushings:
• Housing base sides 8 x M 20 and 2 x M 25
• Housing base rear wall 4 x M 25
Dimensions (W x H x D) 140 x 222 x 70 mm
Weight Approx. 0.8 kg
Housing material Plastic (ABS)
Housing color Papyrus white (RAL 9018)
Environmental conditions Protection category according
to EN 60529
• Without air return IP 20
• With pipe section 100 mm/pipe
bend
IP 42
• With air return IP 54
Permissible temperature range:
• FAS‑420‑TM series Aspirating
Smoke Detector
-20 °C to +60 °C
• PVC pipe system 0 °C to +60 °C
• ABS pipe system -40 °C to +80 °C
Permissible relative humidity
(noncondensing)
Max. 95%
Special features Sound power level
(at 9 V fan voltage) EN27779, 1991
40 dB(A)
Response sensitivity
(light obscuration)
0.5 to 2.0%/m
Life cycle of fan (at 12 V and 24 °C) 60,000 hrs