FIRERAY5000-EN Linear beam detector

دریافت دیتاشیت

Technical Specifications
Electrical Operating voltage 14 V DC (-10%) to 36 V DC (+10%)
Current consumption
• In standby (1 detector head) ≤ 6 mA @ 36 V DC
• In standby (2 detector heads) ≤ 8,5 mA @ 36 V DC
• In alignment mode
(with 1 or 2 detector heads)
≤ 37 mA @ 36 V DC
Reset control by power disruption > 5 s
Alarm relay (contact load) 100 mA @ 36 V
Fault relay (contact load) 100 mA @ 36 V
'Mechanics LED indicators for
• Alarm Flashes red every 10 s
• Fault Flashes yellow every 10 s
• Operation Flashes green every 10 s
Dimensions (W x H x D)
• Detector 134 x 131 x 134 mm
• Prism reflector 100 x 100 x 10 mm
• Control unit 202 x 230 x 87 mm
Housing
• Color Light gray/black
• Materia C6600, non-flammable
Weight
• Detector 500 g
• Prism reflector 100 g
• Control unit 1000 g
Environmental conditions Protection class as per EN 60529 IP 54
Permissible operating temperature -10 °C to 55°C
Planning Permissible distance
detectorreflector
Min. 8 m – max. 50 m
•with FRay5000‑LR‑Kit Long
Range Kit
Min. 50 m – max. 100 m
Lateral detection
(on either sides of the light beam)
Max. 7.5 m (heed local guidelines!)
Connectable detectors per system
controller
1 to 2
Special features Optical wavelength 850 nm
Tolerance of the axial deviation
• Detector ± 0.3°
• Reflective prism ± 5.0°