FIRERAY5000-EN Linear beam detector
| Technical Specifications | ||
| Electrical | Operating voltage | 14 V DC (-10%) to 36 V DC (+10%) |
| Current consumption | ||
| • In standby (1 detector head) | ≤ 6 mA @ 36 V DC | |
| • In standby (2 detector heads) | ≤ 8,5 mA @ 36 V DC | |
| • In alignment mode (with 1 or 2 detector heads) |
≤ 37 mA @ 36 V DC | |
| Reset control by power disruption | > 5 s | |
| Alarm relay (contact load) | 100 mA @ 36 V | |
| Fault relay (contact load) | 100 mA @ 36 V | |
| 'Mechanics | LED indicators for | |
| • Alarm | Flashes red every 10 s | |
| • Fault | Flashes yellow every 10 s | |
| • Operation | Flashes green every 10 s | |
| Dimensions (W x H x D) | ||
| • Detector | 134 x 131 x 134 mm | |
| • Prism reflector | 100 x 100 x 10 mm | |
| • Control unit | 202 x 230 x 87 mm | |
| Housing | ||
| • Color | Light gray/black | |
| • Materia | C6600, non-flammable | |
| Weight | ||
| • Detector | 500 g | |
| • Prism reflector | 100 g | |
| • Control unit | 1000 g | |
| Environmental conditions | Protection class as per EN 60529 | IP 54 |
| Permissible operating temperature | -10 °C to 55°C | |
| Planning | Permissible distance detectorreflector |
Min. 8 m – max. 50 m |
| •with FRay5000‑LR‑Kit Long Range Kit |
Min. 50 m – max. 100 m | |
| Lateral detection (on either sides of the light beam) |
Max. 7.5 m (heed local guidelines!) | |
| Connectable detectors per system controller |
1 to 2 | |
| Special features | Optical wavelength | 850 nm |
| Tolerance of the axial deviation | ||
| • Detector | ± 0.3° | |
| • Reflective prism | ± 5.0° | |
مطالب مرتبط: