FIRERAY3000 Linear beam detector

دریافت دیتاشیت

Technical Specifications
Electrical Operating voltage 12 V DC to 36 V DC (±10%)
Current consumption
• Control Unit in standby
(with 1 or 2 receivers)
14 mA @ 36 V DC
• Transmitter in standby 8 mA @ 36 V DC
Reset control by power disruption > 20 s
Fire and fault relay (contact load) Resistive VFCO 2 A @ 30 V
'Mechanics LED indicators for
• Control Unit Red = Fire
Amber = Fault
Green = System OK
• Receiver Red = Fire
Alignment LEDs for single person alignmen
Dimensions (W x H x D)
• Transmitter & Receiver 78 x 77 x 161 mm
• Control unit 203 x 124 x 72 mm
Housing
• Color Light gray/black
• Materia C6600, non-flammable
Weight
• Detector 500 g
500 g 100 g
• Control unit 1000 g
Environmental conditions Protection class as per EN 60529 IP 54
Permissible operating temperature -10 °C to 55°C
Planning Permissible distance
transmitterreceiver
Min. 5 m – max. 100 m
Connectable detectors per
system controller
2 Transmitter and 2 Receiver
Special features Optical wavelength 850 nm