FAP-420/FAH-420 Automatic Fire Detectors LSN improved version
Technical Specifications | ||
Electrical | Operating voltage | 15 V DC to 33 V DC |
Current consumption | < 0.55 mA | |
Alarm output | Per data word by two-wire signal line |
|
Indicator output | Open collector connects 0 V over 1.5 kΩ through, max. 15 mA |
|
Mechanics | Dimensions | |
• Without base | Ø 99.5 x 52 mm | |
• With base | Ø 120 x 63.5 mm | |
Housing | ||
• Material | Plastic, ABS (Novodur) | |
• Color | White, similar to RAL 9010, matt finish |
|
Weight | Without / with packaging | |
• FAP-DOTC 420 | Approx. 80 g / Approx. 135 g | |
• FAP-DOT 420, FAP‑DO 420 | Approx. 75 g / Approx. 125 g | |
• FAP-OTC 420 | Approx. 80 g / Approx. 125 g | |
• FAP-OT 420, FAP‑O 420, FAP‑O 420 KKW, FAH‑T 420, FAH‑T 420 KKW |
Approx. 75 g / Approx. 115 g | |
Environmental conditions | Permissible operating temperature | |
• FAP-DOTC420 • FAP-OTC 420 |
-10 °C to +50 °C | |
• FAP-DOT420 • FAP-OT 420 • FAH-T 420 • FAH‑T 420 KKW |
-20 °C to +50 °C | |
• FAP-DO420 • FAP-O 420 • FAP‑O 420 KKW |
-20 °C to +65 °C | |
Permissible storage temperature | ||
• FAP-DOTC420 | -20 °C to +50 °C | |
• FAP-DOT420 | -25 °C to +80 °C | |
• FAP-DO420 | -25 °C to +80 °C | |
Permissible relative humidity | 95% (non-condensing) | |
Permissible air speed | 20 m/s. | |
Protection class as per EN 60529 | IP 40, IP 43 detector base with damp room seal |
|
Further characteristics | Response sensitivity | |
• Optical part | In accordance with EN 54 T7 (programmable) |
|
• Thermal maximum part | > 54 °C / >69 °C | |
• Thermal differential part: FAH-T 420, FAH‑T 420 KKW |
A2S / A2R / A1 / A1R / BS / BR, in line with EN 54‑5 (programmable) |
|
• Thermal differential part: FAP‑DOTC420, FAP‑DOT420, FAP‑OTC420, FAP‑OT420 |
A2S / A2R / BS / BR, in line with EN 54‑5 (programmable) |
|
• Gas sensor | In ppm range | |
Individual display | LED red | |
Color code | ||
• FAP-DOTC420 | 2 yellow concentric loops | |
• FAP-OTC 420 | Yellow loop | |
• FAP-DOT 420 | 2 black concentric loops | |
• FAP-OT 420 | Black loop | |
• FAP-DO420 | 2 gray concentric loops | |
• FAP-O 420, FAP‑O 420 KKW |
No marking | |
• FAH-T 420, FAH‑T 420 KKW |
Red loop | |
Planning | Monitoring area | |
• FAP‑DOTC 420, FAP‑DOT 420, FAP‑DO 420, FAP‑OTC 420, FAP‑OT 420, FAP‑O 420 |
Max. 120 m2 (Heed local guidelines!) | |
• FAH-T 420 FAH‑T 420 KKW |
Max. 40 m2 (Heed local guidelines!) | |
Maximum installation height | 16 m (Heed local guidelines!) | |
• FAP‑DOTC 420, FAP‑DOT 420, FAP‑DO 420, FAP‑OTC 420, FAP‑OT 420, FAP‑O 420, FAP‑O 420 KKW |
Max. 16 m (Heed local guidelines!) | |
• FAH-T 420, FAH‑T 420 KKW | Max. 7.5 m (Heed local guidelines!) |