AVENAR detector 4000
Technical Specifications | ||
Electrical | Operating voltage | 15 V DC to 33 V DC |
Current consumption | < 0.55 mA | |
Alarm output | Per data word by two-wire signal line |
|
Indicator output | Open collector connects 0 V over 1.5 kΩ through, max. 15 mA |
|
'Mechanics | Dimensions | |
• Without base | Ø 99.5 x 52 mm | |
• With base | Ø 120 x 63.5 mm | |
Housing | ||
• Material | Plastic, ABS (Novodur) | |
• Color | White, similar to RAL 9010, matt finish | |
Weight | Without / With packaging | |
• FAP-425-DOTC-R | Approx. 85 g / Approx. 130 g | |
• FAP-425-DO-R, FAP‑425- DOT-R | Approx. 80 g / Approx. 120 g | |
• FAP-O-425-R / FAP‑425- OT-R / FAH‑425-T-R |
Approx. 80 g / Approx. 120 g | |
• FAP-425-O / FAP-425-OT | Approx. . 75 g / Approx. 115 | |
Environmental conditions | Permissible operating temperature | |
• FAP-425-DOTC-R | -10 °C to +50 °C | |
• FAP-425-DOT-R / FAP-425-OT-R / FAH‑425-T-R / FAP-425-OT |
-20 °C to +50 °C | |
• FAP-425-DO-R / FAP-425-O-R / FAP‑425-O |
-20 °C to +65 °C | |
Permissible storage temperature | ||
• FAP-425-DOTC-R | -20 °C to +50 °C | |
• All versions (except for FAP-425-DOTC-R) |
-25 °C to +80 °C | |
Permissible relative humidity | 95% (non-condensing) | |
Permissible air speed | 20 m/s. | |
Protection class as per EN 60529 | IP 40, IP 43 detector base with damp room seal |
|
Further characteristics | Response sensitivity | |
• Optical part | In accordance with EN54-7 (programmable) |
|
• Thermal maximum part | > 54 °C / >69 °C | |
• Thermal differential part: • FAH-425-T-R |
A2S / A2R / A1 / A1R / BS / BR, in line with EN 54‑5 (programmable) |
|
• Thermal differential part: • FAP‑425-DOTC-R / FAP‑425-DOT-R / FAP‑425‑OT-R / FAP‑425-OT |
A2S / A2R / BS / BR, in line with EN 54‑5 (programmable) |
|
• Gas sensor | In ppm range | |
Individual display | LED red | |
Color code | ||
• FAP-425-O-R / FAP-425- O | No marking | |
• FAP-425-OT-R / FAP-425-OT | Black loop | |
• FAH-425-T-R | Red loop | |
• FAP-425-DO-R | 2 gray concentric loops | |
• FAP-425-DOT-R | 2 black concentric loops | |
• FAP-425-DOTC-R | 2 yellow concentric loops | |
Planning | Monitoring area | |
• All versions (except for FAH-425-R) | Max. 120 m2 | |
• FAH-425-T-R | ax. 40 m2 | |
Maximum installation height | ||
• All versions (except for FAH-425-R) | Max. 16 m | |
• FAH-425-T-R | Max. 7.5 m |