FCS-320-TM Series Conventional Aspirating Smoke Detectors
Technical Specifications | ||
Electrical | Operating voltage | 10 V DC . . . 30 V DC |
Current consumption | ||
• In standby | < 4 mA @ 24 V | |
• In alarm/malfunction | < 15 mA | |
Reset control by power disruption | > 5 s | |
Alarm relay (contact load) | Open contact, potential free (2 A @ 30 V DC) |
|
Fault relay (contact load) | Break contact element, potential free (2 A @ 30 V DC) |
|
Mechanics | LED indicators for | |
• Alarm | Red | |
• Malfunction | Yellow | |
Operation | Yellow flashing once in 10 seconds | |
• Limit of the readjustment for contamination/aging |
Yellow flashing once in 2 seconds | |
Dimensions (W x H x D) | ||
• Fireray 50/100RV | 126 x 210 x 120 mm | |
• Prism reflector | 100 x 100 x 9.5 mm | |
Housing Color | Light gray/black | |
Housing material | ABS, non-flammable | |
Weight | 670 g | |
Environmental conditions | Protection class as per EN 60529 | IP 50 |
Permissible operating temperature | -30 °C . . . 55 °C | |
Planning | Permissible distance detector-reflector | |
• Fireray 50RV | Min. 5 m - max. 50 m | |
• Fireray 100RV | Min. 50 m - max. 100 m | |
Side detection width (on both sides of the light beam) |
Max. 7.5 m (Heed local guidelines!) | |
Special features | Optical wavelength | 880 nm |
Adjustable alarm threshold values | 2.50 dB (25%) 3.74 dB (35%) 6.02 dB (55%) |
|
Tolerance of the axial deviation (at 35% sensitivity) |
||
• Detector | ± 0.8° | |
• Prism reflector | ± 5.0° |