| Technical Specifications | ||
| Electrical | Operating voltage | 10 V DC . . . 30 V DC |
| Current consumption | ||
| • In standby | < 4 mA @ 24 V | |
| • In alarm/malfunction | < 15 mA | |
| Reset control by power disruption | > 5 s | |
| Alarm relay (contact load) | Open contact, potential free (2 A @ 30 V DC) |
|
| Fault relay (contact load) | Break contact element, potential free (2 A @ 30 V DC) |
|
| Mechanics | LED indicators for | |
| • Alarm | Red | |
| • Malfunction | Yellow | |
| Operation | Yellow flashing once in 10 seconds | |
| • Limit of the readjustment for contamination/aging |
Yellow flashing once in 2 seconds | |
| Dimensions (W x H x D) | ||
| • Fireray 50/100RV | 126 x 210 x 120 mm | |
| • Prism reflector | 100 x 100 x 9.5 mm | |
| Housing Color | Light gray/black | |
| Housing material | ABS, non-flammable | |
| Weight | 670 g | |
| Environmental conditions | Protection class as per EN 60529 | IP 50 |
| Permissible operating temperature | -30 °C . . . 55 °C | |
| Planning | Permissible distance detector-reflector | |
| • Fireray 50RV | Min. 5 m - max. 50 m | |
| • Fireray 100RV | Min. 50 m - max. 100 m | |
| Side detection width (on both sides of the light beam) |
Max. 7.5 m (Heed local guidelines!) | |
| Special features | Optical wavelength | 880 nm |
| Adjustable alarm threshold values | 2.50 dB (25%) 3.74 dB (35%) 6.02 dB (55%) |
|
| Tolerance of the axial deviation (at 35% sensitivity) |
||
| • Detector | ± 0.8° | |
| • Prism reflector | ± 5.0° | |