خانه
محصولاتاعلام حریق بوشconventional fire alarm systemAutomatic Fire DetectorsPoint-type Detectors
FCP‑320/FCH‑320 Conventional Automatic Fire Detectors
| Technical Specifications | ||
| Electrical | Operating voltage | 8.5 V DC to 30 V DC |
| Current consumption | < 0.12 mA | |
| Alarm output | Increase in current (alarm resistance 820 Ωor 470 Ω |
|
| Indicator output | Open collector connects 0 V in the event of an alarm over 3.92 kΩ |
|
| Mechanics | Individual display | LED red |
| Dimensions | ||
| • Without base | Ø 99.5 x 52 mm | |
| • With base | Ø 120 x 63.5 mm | |
| Housing material | Plastic, ABS | |
| Housing color | White, similar to RAL 9010, matt finish |
|
| Weight | Without / with packaging | |
| • FCP-OC320 | Approx. 85 g / approx 130 g | |
| • FCP-OT320 / FCP-O320 / FCH-T320 / FCH-T320-FSA |
Approx. 80 g / approx. 120 g | |
| Environmental conditions | Protection class as per EN 60529 | IP 40, IP 43 with detector base with damp room seal |
| Permissible relative humidity | 95% (non-condensing) | |
| Permissible air speed | 20 m/s | |
| Permissible operating temperature | ||
| • FCP-OC320 | -10 °C to +50 °C | |
| • FCP-OT320 | -20 °C to +50 °C | |
| • FCP-O320 | -20 °C to +65 °C | |
| • FCH-T320 / T320-FSA | -20 °C to +50 °C | |
| Planning | Monitoring area | |
| • FCP-OC320, FCP-OT320, FCP-O320 |
Max. 120 m2 (Heed local guidelines!) |
|
| • FCH-T320 | Max. 40 m2 (Heed local guidelines!) |
|
| Maximum installation height | 16 m (Heed local guidelines!) | |
| • FCP-OC320, FCP-OT320, FCP-O320 |
16 m (Heed local guidelines!) | |
| • FCH-T320 | 6 m (Heed local guidelines!) | |
| Special features | Response sensitivity | |
| • Optical part | < 0.2 dB/m, in line with EN 54 T7 | |
| • Thermal maximum part | >54 °C | |
| • Thermal rate-of-rise part (in line with prEN 54‑5) |
FCH-T320: A2R FCH-T320-FSA: A1R |
|
| • Chemical part | In ppm range | |
| Color code | ||
| • FCP-OC320 | Blue ring | |
| • FCP-OT320 | Black ring | |
| • FCP-O320 | No marking | |
| • FCH-T320 / T320-FSA | Red ring | |