FCP‑500 Conventional Automatic Fire Detectors
| Technical Specifications | ||
| Electrical | Operating voltage | 8.5 V DC bis 33 V DC |
| Standby current | ||
| • FCA-500-EU | 3 mA | |
| • FCA-500-E-EU | 24 mA | |
| Alarm current | 47 mA | |
| Fault current | ||
| • FCA-500-EU | 52 mA | |
| • FCA-500-E-EU | 58 mA | |
| Alarm resistance | Indicator output | |
| Fault relay output | NC / C | |
| Indicator output | Relay connects 0 V over 1.5 kΩ | |
| Mechanics | Individual display | Two-color LED, red (alarm), green (test mode) |
| Dimensions | ||
| Detector | Ø 113 x 55 mm | |
| Detector with trim ring | Ø 150 x 55 mm | |
| Detector with cover, base and ceiling mount back box |
Ø 150 x 110 mm | |
| Housing material | Polycarbonate | |
| Housing color | Signal white, RAL 9003 | |
| Front plate color | ||
| FCP‑O 500/ FCP‑OC 500 | Signal white matt | |
| FCP‑O 500‑P/ FCP‑OC 500‑P | Transparent/silver-gray | |
| Weight | Without / with packaging | |
| FCP-OC 500(-P) | 180 g / 370 g | |
| 'FCP-O 500(-P) | '170 g / 360 g | |
| Trim Ring | 30 g / 60 g | |
| Environmental conditions | Protection class as per EN 60529 | |
| FCP‑O 500 (‑P) | IP 53 | |
| FCP‑OC 500 (‑P) | IP 33 | |
| Permissible operating temperature | ||
| FCP‑O 500 (‑P) | -20 °C bis +65 °C | |
| FCP‑OC 500 (‑P) | -10 °C bis +50 °C | |
| Permissible relative humidity | 95% (non-condensing) | |
| Permissible air speed | 20 m/s | |
| Planning | Monitoring area | Max. 120 m2 (Heed local guidelines!) |
| Maximum installation height | Max. 16 m (Heed local guidelines!) |
|
| Minimum installation height | Out of arm's reach Minimum installation height recommended by BOSCH: 2.70 m |
|
| In the case of flush ceiling mounting with ceiling mount back box |
||
| Thickness of the false ceiling | Max. 32 mm | |
| Required bored hole | Ø 130 mm (-1 mm bis +5 mm) | |
| Installation depth | 110 mm Note: Above the false ceiling, a free height of at least 110 mm is required. |
|
| Minimum distance to lamps | 0.5 m | |
| Special features | Detection principle | |
| • FCP‑O 500 (‑P) | Scattered light measuremen | |
| • FCP‑OC 500 (‑P) | Combination of scattered light measurement and combustion gas measurement |
|
| Features | ||
| • All FCP‑500 detectors | Contamination detection Drift compensation(optical section) |
|
| • In addition, for FCP‑OC 500(-P) | Drift compensation in the gas sensor section |
|
| Response sensitivity | ||
| • FCP‑O 500 (‑P) | < 0.18 dB/m ( EN 54‑7) | |
| • FCP‑OC 500 (‑P) | Optical section: < 0.36 dB/m (EN 54‑7) Gas sensor section: in ppm range |
|