FPC-500 Conventional Fire Panel

دریافت دیتاشیت

Technical Specifications
- FPC‑500‑2 FPC‑500‑4 FPC‑500‑8
Detector zones 2 4 8
Max. number of detectors
in accordance
with EN 54‑2
64 128 256
Max. number of detectors
per zone in accordance
with EN 54‑2
32
Max. extension modules 0 1 2
Prog. inputs 1 2
AUX output 1
NAC output 2
Relays 2
Alarm counter 999 alarms
Event history 1000 events
Test history 1000 test events
Electrical

FPC‑500‑2  FPC‑500‑4 FPC‑500‑8
Input voltage 230 VAC +10%/-15%, 50-60 Hz
Max. current consumption AC 275 mA 312 mA 375 mA
Power consumption 80 W
Operating voltage 21.4 VDC to 29 VDC
Imin 70 mA
Imax, a 0.7 A
Imax, b 2.3 A
Zones
• voltage 20 VDC ±1VDC
• current max. 100 mA ±5 mA
• max. cable resistance 22.5 Ω
AUX
• voltage 21 VDC to 29 VDC
• current 500 mA ±10%
• max. cable resistance 22.5 Ω
• fuse 0.75 A @ 60 V
NAC
• voltage 21 VDC to 29 VDC
• current 500 mA ±10% each
• fuse 0.75 A @ 60 V
• max. cable resistance 22.5 Ω
Relay outputs
• contact rating 1 A @ 30 VDC
• max. cable resistance 22.5 Ω
OC outputs No inductive load.
• contact rating 20 mA @ 24 VDC
• max. cable resistance 22.5 Ω
recommended cable
type
Unshielded cable, 0.8 mm cable diameter
to 1.5 mm² cable cross section
Batteries 2 x 7.2 Ah (max.)
• max. internal resistance 800 mΩ
• current consumption 2.3 A
• fuse 5 A @ 60 V
Discharge voltage threshold 21.4 V
Communication parameters
NAC
Normal
• A- 10 – 15 V
• B+ 0 – 0,5 V
Alarm
• A- 0 – 1 V
• B+ 21 – 29 V
Inputs
• Alarm resistor 820 Ω ±5%
• End of line resistor 3.9 kΩ ±1%
Zone (with resistors)
• Alarm resistor 820 Ω ±5% 910 Ω ±5% No dual-detector
 dependency: 680 Ω ±5%
• End of line resistor 3.9 kΩ ±1%
Zone (with EOL-Module)
• Alarm resistor 820 Ω ±5% 910 Ω ±5% No dual-detector
 dependency: 680 Ω ±5%
Mechanics

FPC‑500‑2 FPC‑500‑4 FPC‑500‑8
Dimensions ( H x W x D) 351 x 351 x 90 mm
Weight 2200 g, without batteries
Housing material
• Front ABS+PC
• Back ABS-FR
Housing color
• Front RAL 9003 (signal white)
• Front PANTONE 10 C (cool grey)
Environmental conditions
FPC‑500‑2 FPC‑500‑4 FPC‑500‑8
Protection class as per IEC 60529 IP 30
Protection class as per EN 60950 II
EMC emmission EN 61000-6-3
EMC immunity EN 50130-4
Vibrations EN 60068-2-6
Permissible operating temperature 0°C to +40°C
Permissible storage temperature -10°C to +55°C
Permitted relative humidity 95% non-condensing