FPC-500 Conventional Fire Panel
Technical Specifications | |||
- | FPC‑500‑2 | FPC‑500‑4 | FPC‑500‑8 |
Detector zones | 2 | 4 | 8 |
Max. number of detectors in accordance with EN 54‑2 |
64 | 128 | 256 |
Max. number of detectors per zone in accordance with EN 54‑2 |
32 | ||
Max. extension modules | 0 | 1 | 2 |
Prog. inputs | 1 | 2 | |
AUX output | 1 | ||
NAC output | 2 | ||
Relays | 2 | ||
Alarm counter | 999 alarms | ||
Event history | 1000 events | ||
Test history | 1000 test events | ||
Electrical | |||
FPC‑500‑2 | FPC‑500‑4 | FPC‑500‑8 | |
Input voltage | 230 VAC +10%/-15%, 50-60 Hz | ||
Max. current consumption AC | 275 mA | 312 mA | 375 mA |
Power consumption | 80 W | ||
Operating voltage | 21.4 VDC to 29 VDC | ||
Imin | 70 mA | ||
Imax, a | 0.7 A | ||
Imax, b | 2.3 A | ||
Zones | |||
• voltage | 20 VDC ±1VDC | ||
• current | max. 100 mA ±5 mA | ||
• max. cable resistance | 22.5 Ω | ||
AUX | |||
• voltage | 21 VDC to 29 VDC | ||
• current | 500 mA ±10% | ||
• max. cable resistance | 22.5 Ω | ||
• fuse | 0.75 A @ 60 V | ||
NAC | |||
• voltage | 21 VDC to 29 VDC | ||
• current | 500 mA ±10% each | ||
• fuse | 0.75 A @ 60 V | ||
• max. cable resistance | 22.5 Ω | ||
Relay outputs | |||
• contact rating | 1 A @ 30 VDC | ||
• max. cable resistance | 22.5 Ω | ||
OC outputs | No inductive load. | ||
• contact rating | 20 mA @ 24 VDC | ||
• max. cable resistance | 22.5 Ω | ||
recommended cable type |
Unshielded cable, 0.8 mm cable diameter to 1.5 mm² cable cross section |
||
Batteries | 2 x 7.2 Ah (max.) | ||
• max. internal resistance | 800 mΩ | ||
• current consumption | 2.3 A | ||
• fuse | 5 A @ 60 V | ||
Discharge voltage threshold | 21.4 V | ||
Communication parameters | |||
NAC | |||
Normal | |||
• A- | 10 – 15 V | ||
• B+ | 0 – 0,5 V | ||
Alarm | |||
• A- | 0 – 1 V | ||
• B+ | 21 – 29 V | ||
Inputs | |||
• Alarm resistor | 820 Ω ±5% | ||
• End of line resistor | 3.9 kΩ ±1% | ||
Zone (with resistors) | |||
• Alarm resistor | 820 Ω ±5% 910 Ω ±5% No dual-detector dependency: 680 Ω ±5% |
||
• End of line resistor | 3.9 kΩ ±1% | ||
Zone (with EOL-Module) | |||
• Alarm resistor | 820 Ω ±5% 910 Ω ±5% No dual-detector dependency: 680 Ω ±5% |
||
Mechanics | |||
FPC‑500‑2 | FPC‑500‑4 | FPC‑500‑8 | |
Dimensions ( H x W x D) | 351 x 351 x 90 mm | ||
Weight | 2200 g, without batteries | ||
Housing material | |||
• Front | ABS+PC | ||
• Back | ABS-FR | ||
Housing color | |||
• Front | RAL 9003 (signal white) | ||
• Front | PANTONE 10 C (cool grey) | ||
Environmental conditions | |||
FPC‑500‑2 | FPC‑500‑4 | FPC‑500‑8 | |
Protection class as per IEC 60529 | IP 30 | ||
Protection class as per EN 60950 | II | ||
EMC emmission | EN 61000-6-3 | ||
EMC immunity | EN 50130-4 | ||
Vibrations | EN 60068-2-6 | ||
Permissible operating temperature | 0°C to +40°C | ||
Permissible storage temperature | -10°C to +55°C | ||
Permitted relative humidity | 95% non-condensing |
مطالب مرتبط: