FPC-500 Conventional Fire Panel
| Technical Specifications | |||
| - | FPC‑500‑2 | FPC‑500‑4 | FPC‑500‑8 |
| Detector zones | 2 | 4 | 8 |
| Max. number of detectors in accordance with EN 54‑2 |
64 | 128 | 256 |
| Max. number of detectors per zone in accordance with EN 54‑2 |
32 | ||
| Max. extension modules | 0 | 1 | 2 |
| Prog. inputs | 1 | 2 | |
| AUX output | 1 | ||
| NAC output | 2 | ||
| Relays | 2 | ||
| Alarm counter | 999 alarms | ||
| Event history | 1000 events | ||
| Test history | 1000 test events | ||
| Electrical | |||
| FPC‑500‑2 | FPC‑500‑4 | FPC‑500‑8 | |
| Input voltage | 230 VAC +10%/-15%, 50-60 Hz | ||
| Max. current consumption AC | 275 mA | 312 mA | 375 mA |
| Power consumption | 80 W | ||
| Operating voltage | 21.4 VDC to 29 VDC | ||
| Imin | 70 mA | ||
| Imax, a | 0.7 A | ||
| Imax, b | 2.3 A | ||
| Zones | |||
| • voltage | 20 VDC ±1VDC | ||
| • current | max. 100 mA ±5 mA | ||
| • max. cable resistance | 22.5 Ω | ||
| AUX | |||
| • voltage | 21 VDC to 29 VDC | ||
| • current | 500 mA ±10% | ||
| • max. cable resistance | 22.5 Ω | ||
| • fuse | 0.75 A @ 60 V | ||
| NAC | |||
| • voltage | 21 VDC to 29 VDC | ||
| • current | 500 mA ±10% each | ||
| • fuse | 0.75 A @ 60 V | ||
| • max. cable resistance | 22.5 Ω | ||
| Relay outputs | |||
| • contact rating | 1 A @ 30 VDC | ||
| • max. cable resistance | 22.5 Ω | ||
| OC outputs | No inductive load. | ||
| • contact rating | 20 mA @ 24 VDC | ||
| • max. cable resistance | 22.5 Ω | ||
| recommended cable type |
Unshielded cable, 0.8 mm cable diameter to 1.5 mm² cable cross section |
||
| Batteries | 2 x 7.2 Ah (max.) | ||
| • max. internal resistance | 800 mΩ | ||
| • current consumption | 2.3 A | ||
| • fuse | 5 A @ 60 V | ||
| Discharge voltage threshold | 21.4 V | ||
| Communication parameters | |||
| NAC | |||
| Normal | |||
| • A- | 10 – 15 V | ||
| • B+ | 0 – 0,5 V | ||
| Alarm | |||
| • A- | 0 – 1 V | ||
| • B+ | 21 – 29 V | ||
| Inputs | |||
| • Alarm resistor | 820 Ω ±5% | ||
| • End of line resistor | 3.9 kΩ ±1% | ||
| Zone (with resistors) | |||
| • Alarm resistor | 820 Ω ±5% 910 Ω ±5% No dual-detector dependency: 680 Ω ±5% |
||
| • End of line resistor | 3.9 kΩ ±1% | ||
| Zone (with EOL-Module) | |||
| • Alarm resistor | 820 Ω ±5% 910 Ω ±5% No dual-detector dependency: 680 Ω ±5% |
||
| Mechanics | |||
| FPC‑500‑2 | FPC‑500‑4 | FPC‑500‑8 | |
| Dimensions ( H x W x D) | 351 x 351 x 90 mm | ||
| Weight | 2200 g, without batteries | ||
| Housing material | |||
| • Front | ABS+PC | ||
| • Back | ABS-FR | ||
| Housing color | |||
| • Front | RAL 9003 (signal white) | ||
| • Front | PANTONE 10 C (cool grey) | ||
| Environmental conditions | |||
| FPC‑500‑2 | FPC‑500‑4 | FPC‑500‑8 | |
| Protection class as per IEC 60529 | IP 30 | ||
| Protection class as per EN 60950 | II | ||
| EMC emmission | EN 61000-6-3 | ||
| EMC immunity | EN 50130-4 | ||
| Vibrations | EN 60068-2-6 | ||
| Permissible operating temperature | 0°C to +40°C | ||
| Permissible storage temperature | -10°C to +55°C | ||
| Permitted relative humidity | 95% non-condensing | ||
مطالب مرتبط: